25
Beeper
TheDominionPXincludesabeeper.Itwillringifanyofthecircuit
breakersistrippedorifthecontrolboardtemperaturesensorexceeds80
degreesCelsius(or176degreesFahrenheit).
Thebeeperwillceaseringingwhenthebrokencircuitbreakerconditions
disappearorthecontrolboardtemperaturesensordropsbelow70
degree
sCelsius(or158degreesFahrenheit).
Thetemperaturethresholdsarefactorydefaults,andcanbeuser
configurable.
Ittakesamaximumofthreesecondsforthebeepertostartringingright
afterthecircuitbreakeristripped.
Measurement Accuracy
Voltage(peroutlet): Range0255V,+/5%,3digits,resolution
1V
Current(peroutlet): Range025A,+/5%,3digits,resolution
0.1A