Raritan PX3TS Manual de usuario

Busca en linea o descarga Manual de usuario para Los conmutadores de red Raritan PX3TS. Release Notes Manual de usuario

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 6
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 0
PX 2.6.1 Build 41229
Release Notes, Revision V1 April 11, 2014
For Raritan PX3TS Customers Only Page 1
Release Notes for Raritan PX3TS Firmware Version 2.6.1
Version: PX2 2.6.1 Build 41229 Release Notes, Version 1
Date: April 11, 2014
Effective: Immediately.
Applicability:
This release contains a critical security fix found in OpenSSL (CVE-
2014-0160, details below in the Release 2.6.1 Contains All
Enhancements and Fixes section below), and it is highly recommended
that all PX3TS customers upgrade to this release immediately.
Raritan will not be liable for any security breaches resulting from
older firmware on a unit.
This firmware release is for General Availability (“GA”) on all existing
PX3TS models only. Units in the field can do a firmware upgrade to this
release.
It is NOT supported on the Raritan iPDUs (PX2-nnnn, PX3-nnnn, PXE, or
the BCM24xx).
There is a new User Guide for PX2.6.0 which should be used with this
release. Some custom engineered models may not be supported by this
release. Please check with Raritan Support if you are unsure of the model
number of your unit; it is typically viewable on the GUI Device
Information page, and is printed on a label on the unit.
Caution: Only Power IQ releases 4.1 and higher are compatible with PX2.6.1.
Due to the critical security fix, and other internal enhancements in PX 2.6.1, you
cannot downgrade from Release 2.6.1 build 41229 to ANY prior release. Please
contact Raritan Support with any questions.
Release Status: General Availability (GA) - see Release compatibility information
section below.
Release 2.6.1 contains all enhancements and fixes which are listed below:
1) The resolution for certain sensors has been increased from two (x.xx) to three
(x.xxx) decimal digits, however, accuracy is still the same as before. The
Raritan SNMP MIB contains a value that provides the resolution, and it must
be used to determine the value of sensor reading. The updated SNMP MIB
can be retrieved from the unit itself using the GUI.
Vista de pagina 0
1 2 3 4 5 6

Indice de contenidos

Pagina 1

PX 2.6.1 Build 41229 Release Notes, Revision V1 April 11, 2014 For Raritan P

Pagina 2

PX 2.6.1 Build 41229 Release Notes, Revision V1 April 11, 2014 For Raritan P

Pagina 3

PX 2.6.1 Build 41229 Release Notes, Revision V1 April 11, 2014 For Raritan P

Pagina 4

PX 2.6.1 Build 41229 Release Notes, Revision V1 April 11, 2014 For Raritan P

Pagina 5

PX 2.6.1 Build 41229 Release Notes, Revision V1 April 11, 2014 For Raritan P

Pagina 6

PX 2.6.1 Build 41229 Release Notes, Revision V1 April 11, 2014 For Raritan P

Comentarios a estos manuales

Sin comentarios